Siemens SINAMICS S120 Commissioning Manual page 133

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Procedure
8.
p0100 = 0
9.
p030X[0] = ...
10.
p1900 = 2
Danger
During motor data identification, the drive may cause the motor to move. The EMERGENCY OFF functions
must be fully operational during commissioning. To protect the machines and personnel, the relevant safety
regulations must be observed.
Operation is configured.
11.
p0010 = 0
RDY is lit red, fault F07085 signals that a control parameter has been changed.
12.
p0840[0] =
r0019.0(DO 1)
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
2.8 First commissioning, control mode vector AC Drive in the booksize format
IEC/NEMA motor standard
0 IEC motor (SI units, e.g. kW)
Preset:
Rated motor frequency (p0310): 50 Hz
Specification of the power factor cos φ (p0308)
1 NEMA motor (US units, e.g. hp)
Preset:
Rated motor frequency (p0310): 60 Hz
Specification of the efficiency (p0309)
Note:
When p0100 is changed, all the rated motor parameters are reset.
Rated motor data [MDS]
Only when p0300 < 100 (third-party motor)
Enter the rated motor data in accordance with the rating plate, e.g.
p0304[0] Rated motor voltage [MDS]
p0305[0] Rated motor current [MDS]
p0307[0] Rated motor output [MDS]
p0308[0] Rated motor power factor [MDS] (only when p0100 = 0)
p0309[0] Rated motor efficiency [MDS] (only when p0100 = 1)
p0310[0] Rated motor frequency [MDS]
p0311[0] Rated motor speed [MDS]
p0335[0] Motor cooling type [MDS] *
0: Natural cooling
1: Forced cooling
2 Water cooling
Motor data identification and rotating measurement*
0 Inhibited
1 Motor data identification for rotating motor
2 Motor data identification for a stationary motor
Message A07991 is displayed, motor data identification was activated.
Drive, commissioning parameter filter *
0 Ready
1 Quick commissioning
BI: ON/OFF1 [CDS]
Sets the signal source for STW1.0 (ON/OFF1)
Interconnection with r0019.000 of the drive object Control Unit (DO 1)
Effect: Signal ON/OFF1 from the BOP
Description
Commissioning
Factory
setting
0
-
2
1
0
131