Commissioning
2.2 STARTER commissioning tool
Assigning the IP address and the name
Note
When assigning names to IO devices (e.g. a Control Unit) in Ethernet (SINAMICS
components), then ST conventions (Structured Text) must be complied with. The names
must be unique within Ethernet. "-" and "." are not permitted in the name of an IO device.
Note
The IP address and device name for the Control Unit are stored on the memory card (non-
volatile).
Assignment with STARTER, "Accessible nodes" function
Use STARTER to assign an IP address and a name for the Ethernet interface.
1. Connect the Control Unit to the programming device.
2. Switch on the Control Unit.
3. Open STARTER.
4. Load your project or create a new project.
5. Call the menu "Project > Accessible nodes" or click on the symbol
6. Select the bus node entry and select the shortcut menu "Edit Ethernet node...".
7. In the dialog "Edit Ethernet nodes", enter the device name for the Ethernet interface.
66
to search for available nodes in the Ethernet.
The SINAMICS drive unit is identified and displayed as bus participant Drive unit_1 with
IP address 169.254.11.22.
– Click on the "Assign Name" button.
– If no entry is in the subnet mask, enter 255.255.0.0 in the subnet mask for the IP
configuration.
– Then click the "Assign IP configuration" button.
– Close the Information window "The parameters were transferred successfully".
– Click on the "Close" button.
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
"Accessible nodes"
Commissioning Manual