What to do?
3.
Configure the
infeed
3.1
The infeed
configuration
wizard
3.2
Inserting an infeed
unit
3.3
3.4
Configuration -
additional data
3.5
Configuring the
infeed unit process
data exchange
3.6
Configuration,
summary
Caution
If the infeed is controlled by a Control Unit other than that used for the Motor Module, then the "Ready" signal for the infeed
r0863.0 must be connected with drive parameter p0864 "Infeed ready" via a digital input/output. If this is not taken into
account, the infeed may be damaged.
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
2.7 First commissioning, vector control mode in the chassis format
1. Call the menu "Project > Disconnect from target system" in
order to change to offline mode.
2. Double-click in the project tree on "Infeeds".
3. Double-click on "Insert infeeds".
The configuration wizard for the infeeds is opened.
If the infeed is connected with the Control Unit via DRIVE-CLiQ,
then the automatically determined data from the electronic rating
plate are displayed in the wizard.
If there is no DRIVE-CLiQ connection to the Control Unit, then
you must manually enter the data of the infeed unit using the
wizard.
1. Enter a name for the infeed unit.
2. Select the type.
3. Click on "OK".
1. Select the line voltage range.
2. Select the cooling type.
3. Select the baud rate.
4. Select the power rating.
5. Click on "Continue >".
1. Activate the line/DC link identification when switching-on for
the first time.
2. Accept the device supply voltage from the previous window.
The rated line frequency is determined automatically.
3. Make sure that the option "Line filter available" is activated.
4. For an infeed in the "booksize" format, select a line filter.
You can select one from several versions.
5. Click on "Continue >".
One of three telegrams can be selected for communication: 370,
371 and 999.
1. For the example, select "[ 999] Free telegram configuration
with BICO".
2. Click on "Continue >".
Configuration of the infeed unit completed. A summary is
displayed.
1. Click on "Complete".
How to do it?
Commissioning
Comment
Infeed
If the line environment or
DC link components are
changed, line/DC link
identification should be
repeated.
-
-
-
-
The infeed unit data can be
copied to the clipboard for
plant documentation
purposes and then added
to a text program, for
example.
121