Siemens SINAMICS S120 Commissioning Manual page 75

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4. Call the menu "Project > Accessible nodes" or click on the symbol
5. Right click on the bus node entry to open the shortcut menu "Edit Ethernet node ...".
6. Under "Set IP configuration", enter the IP address that you selected (e.g. 169.254.11.33)
7. Click on the "Set IP Configuration" button.
8. Click on the "Update" button.
9. In the "Device name" field, enter the name that you have selected.
10. Then click on the "Assign Name" button.
11. Click on the "Update" button.
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
nodes".
– The search is performed for available nodes connected to PROFINET.
– The Control Unit is identified and displayed under "Accessible nodes" as the bus node
with the IP address 0.0.0.0, without any type information.
Figure 2-12
Bus nodes found
– In the selection window that opens "Edit Ethernet node" you will also see the MAC
address.
and the subnet mask (e.g. 255.255.0.0).
– The data transfer is confirmed.
– The bus node is identified as drive unit.
– The address and the type are specified.
In the "Edit Ethernet node" selection window you can also assign a device name to the
drive unit that has been detected.
– The data transfer is confirmed.
– The bus node is detected as drive unit and is consecutively numbered.
– The address, device name and the type are specified.
Commissioning
2.2 STARTER commissioning tool
"Accessible
73