Diagnostics
3.2 Diagnostics via STARTER
Offset
The offset is applied additively to the signal to be output. The signal to be output can thus be
displayed within the measuring range.
Limitation
● Limitation On
● Limitation off
Example of measured value output via a measuring socket
The actual speed (r0063) is to be output for a drive via measuring socket T1.
The following settings should be made:
1. Connect and set the measuring device.
2. Interconnect the signal (e.g. STARTER).
3. Parameterize the signal characteristic (scaling, offset, limitation).
Function diagrams (see SINAMICS S120/S150 List Manual)
● 8134 measuring sockets
Overview of important parameters (see SINAMICS S120/S150 List Manual)
Adjustable parameters
● p0771[0...2] CI: Measuring sockets signal source
● p0777[0...2] Measuring sockets characteristic value x1
● P0778[0...2] Measuring sockets characteristic value y1
● p0779[0...2] Measuring sockets characteristic value x2
● p0780[0...2] Measuring sockets characteristic value y2
● p0783[0...2] Measuring sockets offset
● p0784[0...2] Measuring sockets limit on/off
230
If signals are output outside the permissible measuring range, the signal is limited to 4.98
V or to 0V.
The output of signals outside the permissible measuring range causes a signal overflow.
In the event of an overflow, the signal jumps from 0 V to 4.98 V or from 4.98 to 0 V.
Interconnect the connector input (CI) belonging to the measuring socket with the desired
connector output (CO):
CI: p0771[1] = CO: r0063
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Commissioning Manual