Commissioning
2.7 First commissioning, vector control mode in the chassis format
What to do?
6.4
Setpoint
configuration
7.
Load parameters
to device
8.
Configuration,
motor temperature
126
Specify setpoint:
p1001 = 0 Fixed setpoint 1
p1002 = 40 Fixed setpoint 2
p1020 = r0722 Fixed speed setpoint selection
r1024 = p1070 Fixed setpoint active
1. Select the drive unit in the project tree.
2. Call the "Connect target device" shortcut menu.
3. Then call "Target device" > "Load to target device" shortcut
menu.
For the setting, p0340 must be 0. If p0340 >< 0, then the
temperature sensor selection is locked.
1. Make the following settings:
–
the way in which the motor temperature is received
–
the temperature sensor type
–
for overtemperature, the response to alarm and fault (no
reduction of I
).
max
–
the alarm message when a sensor fails
–
the delay time to 0.100 s
–
the warning threshold to 120.0 C
–
the fault threshold to 155.0 °C
How to do it?
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Comment
A setpoint of 0 (0 signal) or
40 (1 signal) is defaulted
via digital input 7. This
setpoint is then applied to
the main setpoint p1070.
See function diagram
[3010]
Position cursor on drive
unit and right-click.
Commissioning Manual