Braking Modules Booksize Format - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3.1.2.6

Braking Modules booksize format

Table 3- 20
Meaning of the LEDs on the Braking Module booksize
LED
Color
READY
-
Off
Green
Continuous
light
Red
Continuous
light
DC LINK
-
Off
Green
Flashing
light
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
State
Electronic power supply is missing or outside permissible
tolerance range.
Component deactivated via terminal.
Component is ready to operate.
Enable signal missing (input terminal)
Overtemperature
Overcurrent trip
I
t monitoring responded
2
Ground fault/short circuit
Note:
In the event of an overtemperature, the error cannot be
acknowledged until a cooling time has elapsed.
There is no DC link voltage or the electronic power supply is
missing or outside permissible tolerance range.
Component not active.
Component active (DC link discharge via braking resistor in
progress).
Description, cause
Diagnostics
3.1 Diagnostics via LEDs
Remedy
Diagnose fault (via
output terminals) and
acknowledge it (via
input terminal)
199

Advertisement

Table of Contents
loading

Table of Contents