Preparation for commissioning
1.5 Rules for wiring with DRIVE-CLiQ
Mixed operation of servo control and U/f open-loop control
In mixed operation with servo control and U/f control, one axis in servo control at 125 µs
uses exactly as much computing performance as two axes in U/f control at 500 µs. In
conjunction with servo control, a maximum of 11 axes are permitted (1 servo plus 10 vector
U/f).
Table 1- 9
Mixed operation of vector control and U/f open-loop control
In mixed operation with vector control and U/f control, one axis in vector control at 250 µs
uses exactly as much computing performance as two axes in U/f control at 500 µs. In
conjunction with vector control, a maximum of 11 axes are permitted (1 vector plus 10 U/f).
Table 1- 10
34
Number of axes for mixed servo control operation
Number of axes in servo control
6
125 µs
5
125 µs
4
125 µs
3
125 µs
2
125 µs
1
125 µs
0
Number of axes for mixed vector control operation
Number of axes in vector control
6
500 µs
5
500 µs
4
500 µs
3
500 µs
2
500 µs
1
500 µs
0
3
62.5 µs
2
62.5 µs
1
62.5 µs
0
3
250 µs
2
250 µs
1
250 µs
0
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Number of axes in U/f control
0
2
500 µs
4
500 µs
6
500 µs
8
500 µs
10
500 µs
12
500 µs
Number of axes in U/f control
0
2
500 µs
4
500 µs
6
500 µs
8
500 µs
10
500 µs
12
500 µs
Commissioning Manual