Diagnostics
3.1 Diagnostics via LEDs
3.1.2.5

Single Motor Module / Double Motor Module / Power Module

Table 3- 19
Meaning of the LEDs on the Motor Module
State
Ready
DC link
Off
Off
Green
Off
Orange
Red
Orange
Orange
Red
Green / red
flashing light
0.5 Hz
Green / red
flashing light
2 Hz
Green /
orange
or
Red / orange
Hazardous DC link voltages may be present at any time regardless of the state of the "DC
link" LED.
The warning information on the component must be carefully observed!
198
Electronic power supply is missing or outside
permissible tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED state when activated
via p0124 = 1.
DANGER
Description, cause
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Remedy
Check the line voltage
Remedy and acknowledge
fault
Carry out a POWER ON
Commissioning Manual