Commissioning
2.7 First commissioning, vector control mode in the chassis format
What to do?
5.6
Configuring
process data
exchange
5.7
Summary
Note
The reference parameters and limit values in the STARTER can be protected from being automatically overwritten by
p0340 = 1. You can find this function in STARTER under Drive -> Configuration-> Blocked list tab.
6.
Enable signals and
BICO
interconnections
6.1
Active Line Module 
124
For communication, you can select the PROFIdrive telegram
from various telegrams.
1. For the example, select "[ 999] Free telegram configuration
with BICO".
2. Click on "Continue >".
The configuration of the drive train has been completed. A
summary is displayed.
1. Click on "Complete".
The enable signals for the infeed and the two drives must be
realized via the digital inputs on the Control Unit.
Enable signals for the Active Line Module:
p0840 = 722.4 ON/OFF1
p0844 = 722.5 OFF2
p0852 = 722.6 Enable operation
How to do it?
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Comment
-
The drive data can be
copied to the clipboard for
plant documentation
purposes and then added
to a text program, for
example.
Note:
If an Active Line Module is
used, to enable the infeed
unit, a signal source other
that that used for the Motor
Module must be used.
See function diagram
[8920]