88 • Feldbus Coupler/Controller
Fieldbus Controller 750-806
DIP switches 7 and 8 are used to set the desired baud rate.
1
2
3
4
5
6
7
8
Fig. 3-31: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) of the
station with MAC ID 1.
2.

3.2.9.3 Configuration with Static and Dynamic Assembly

In this example, the software RSNetWorx Rev:3.00.00 of Allan-Bradley and
SLC500 with a 1747-SDN Scanner Module is used.
The inputs are mapped using the static Assembly and the outputs are mapped
with the dynamic Assembly.
The node in the example consists of the following I/O modules:
Fig. 3-32: Example for a fieldbus node
1. Starting Software and EDS file load
1. Start the configuration software RSNetWorx.
2. Load the EDS file "750-806_1.EDS" for the fieldbus Controller in
3. Now follow the Wizard instructions.
ON
Then switch on the Controller supply voltage.
1
DI DI
DI DI
402
402
RSNetWorx.
For this click on "Tools/ EDS Wizard" and choose the EDS-file to load.
Note
You can download the EDS file 750-806_1.EDS from the Internet under:
www.wago.com
Baud rate
*)
125 kBaud
250 kBaud
500 kBaud
g012541x
not allowed
*)
Presetting
2
3
4
5
6
DODO DODO AI AI
DODO
516
516
516
467
DIP7
DIP8
OFF
OFF
ON
OFF
OFF
ON
ON
ON
7
8
AO AO
550
600
WAGO-I/O-SYSTEM 750
g012553x