142 • Application in Explosive Environments
Classification Meeting CENELEC and IEC
6.3.4 Temperature Classes
The maximum surface temperature for electrical components of explosion
protection group I is 150 °C (danger due to coal dust deposits) or 450 °C (if
there is no danger of coal dust deposit).
In line with the maximum surface temperature for all ignition protection
types, the electrical components are subdivided into temperature classes, as
far as electrical components of explosion protection group II are con-
cerned. Here the temperatures refer to a surrounding temperature of 40 °C
for operation and testing of the electrical components. The lowest ignition
temperature of the existing explosive atmosphere must be higher than the
maximum surface temperature.
Temperature Classes
T1
T2
T3
T4
T5
T6
The following table represents the division and attributes of the materials
to the temperature classes and material groups in percent:
Temperature Classes
T1
26.6 %
Explosion Group
IIA
80.2 %
Maximum Surface
Temperature
450 °C
300 °C
200 °C
135 °C
100 °C
85°C
T2
T3
42.8 %
25.5 %
94.9 %
IIB
IIC
18.1 %
0.7 %
Ignition Temperature
of the Combustible Materials
> 450 °C
> 300 °C to 450 °C
> 200 °C to 300 °C
> 135 °C to 200 °C
>100 °C to 135 °C
> 85 °C to 100 °C
T4
T5
4.9 %
0 %
*
Number of classified materials
*
T6
Total
0.2 %
432
*
Total
436
WAGO-I/O-SYSTEM 750