4. Do not change the value for the ID#37 "PLC fieldbus Input variables"
5. Confirm the setting by clicking on the "OK" button.
6. Double-click on the scanner icon to start the configuration.
7. Select the "Scanlist" register card.
8. Click on the button with the arrow to the right in order to take over the
9. Click on the "Edit I/O Parameters..." button.
10. Activate the poll function by clicking on the field located in front of
11. Enter 6 bytes in the "TX-Size" dialog box. They are receipt bytes for the
12. Then click on the "OK" button to take over the parameters.
WAGO-I/O-SYSTEM 750
DeviceNet
which is 0. Enter 4 for the ID#38 "PLC fieldbus Output variables".
The dialog window "1797-SDN Scanner Module" opens.
DeviceNet Controller 750-806 in the left-hand window "Available De-
vices" into the "Scanlist" window.
"Polled".
The field is now ticked which permits the entry for TX and RX.
inputs.
Enter 4 bytes for the PFC input variables in the "RX-Size" dialog box. The
number of these bytes results from the following determinations in the dy-
namic assembly for the outputs. This simultaneously defines that only the
PFC input variables and no physical outputs are to be written by the mas-
ter.
A window appears indicating that several I/O data will not be mapped.
Confirm the question of whether or not you wish to continue by clicking
on the "Yes" button.
Feldbus-Koppler/-Controller • 91
Fieldbus Controller 750-806