WAGO 750-306 Technical Description page 136

Modular i/o system devicenet
Hide thumbs Also See for 750-306:
Table of Contents

Advertisement

136 • DeviceNet
Configuration / Parametering with the Object Model
5.6.2.2.16
Class 172 (0xAC) Output Fieldbus Variable UDINT
PLC output byte 1..128
Max. instance: 128
5.6.2.2.17
Class 173 (0xAD) Output Fieldbus Variable UDINT
PLC output byte 1..128
Max. instance: 128
Starts with 2 bytes offset
(the 2nd and 3rd UINT (class168 / instance 2 and 3)
= 1st UDINT (class173 / instance 1) etc.)
5.6.2.2.18
Class 100 (0x64) - Attribute 44/100/101
Attribut ID
44
(0x2C)
100 (0x64)
101 (0x65)
Example:
The example comes from the DeviceNet Coupler point of view:
-> Configuration Coupler:
-> BK_FBINP_VAR_CNT = 0; BK_FBOUT_VAR_CNT = 0
-> BK_FBINP_VAR_CNT = 4; BK_FBOUT_VAR_CNT = 3
5.6.2.2.19
Identity Class 1 (0x01)
Instance 1:
Attribut ID
10 (0x0A)
Used in Coupler
Access rule
Specific
Get/Set
Specific
Get/Set
Specific
Get/Set
poll connection: -> 12 byte produced
-> 10 byte consumed
poll connection:
-> 15 byte produced
(12 byte input process image + 3 byte PLC output fieldbus variables)
-> 14 byte consumed
(10 byte output process image + 4 byte PLC input fieldbus variables)
Used in Coupler
Access rule
required
Get/Set
Attribute
Data type
name
BK_SAVE_
UINT
DYN_ASS_
INST
BK_FBINP_
UINT
VAR_CNT
BK_FBOUT
UINT
_VAR_CNT
input process image 12 byte,
output process image 10 byte
Attribute name Data type
Heartbeat
USINT
Interval
Brief description of the attribute
Save dynamic created instances in non
volatile memory (after power up all
saved instances are automatically
created )
0: save no dynamic instances
1: save dynamic instances
Defines the number of bytes from the
PLC-fieldbus-variables (inputs) which
will be added to the assembly object
(this count will be added to the consu-
med path – assembly instances 1..3)
Defines the number of bytes from the
PLC-fieldbus-variables (outputs)
which will be added to the assembly
object (this count will be added to the
produced path – assembly instances
4..9)
Description of the attribute
Interval between 2 Heartbe-
at messages in seconds
WAGO-I/O-SYSTEM 750
DeviceNet
Default
Value
0