The maximum input current of the 24 V system supply amounts to 500 mA.
The exact electrical consumption (I
formulas:
Coupler/Controller
I(5 V) ges. =
750-613
I(5 V) ges. =
Input current I(24 V) =
Note
If the electrical consumption of the power supply point for the 24 V-system
supply exceeds 500 mA, then the cause may be an improperly aligned node
or a defect.
During the test, all outputs, in particular those of the relay modules, must be
active.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
) can be determined with the following
(24 V)
Sum of all current consumptions of the connected bus modules
+ internal current consumption coupler / controller
Sum of all current consumptions of the connected bus modules
5 V / 24 V * I(5 V) ges./ η
η = 0.87 (at nominal load)