4. DIP switches 7 and 8 are used to set the desired baud rate.
ON
Fig. 3-11: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) of the
station with MAC ID 1.
5. Then switch on the coupler supply voltage.

3.1.7.3 Configuration with Static Assembly

In this example, the software WAGO NETCON is used for the configuration.
The node in the example consists of the following I/O modules:
Fig. 3.1.7-12 Example Fieldbus node
1. Starting Software and EDS file load
6. Start the configuration software WAGO NETCON.
7. Load an EDS file for the fieldbus coupler in WAGO NETCON, i. e. "750-
346.EDS".
For this click on "File/ Copy EDS" and choose the EDS-file to load.
Note
You can download the EDS files for the fieldbus coupler from the Internet
under: www.wago.com.
8. Upon downloading the EDS file into WAGO NETCON, you can create a new
project and start configuring your network.
WAGO-I/O-SYSTEM 750
DeviceNet
Baud rate
8
7
125 kBaud
6
5
4
250 kBaud
3
2
500 kBaud
1
g012551x
not allowed
*)
1
2
3
4
5
6
DI DI
DODO
DODO DODO AI AI
AO AO
402
516
516
516
467
550
Fieldbus Coupler
Fieldbus Coupler 750-346
DIP7
*)
OFF
ON
OFF
ON
Presetting
7
600
• 55
DIP8
OFF
OFF
ON
ON
g012554x