5.6.2.1.8 Coupler configuration object (0x64):
Instance 0:
Attribute
ID
1
2
Instance 1:
Attribute
ID
1
2
3
4
5
6
7
8
9
10
11
12
13
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Used in
Access
Name
buscoupler
rule
required
get
Revision
required
get
Max
instance
Used in
Access
Name
buscoupler
rule
specific
get/set
Bk_Module
No
specific
get/set
Bk_TableNo USINT
specific
get/set
Bk_Register
No
specific
get/set
Bk_Data
specific
get
ProcessState
specific
get
DNS_i_Trm
nldia (**)
specific
get
CnfLen.
AnalogOut
specific
get
CnfLen.
AnalogInp
specific
get
CnfLen.
DigitalOut
specific
get
CnfLen.
DigitalInp
specific
get/set
BK_FAULT
_REACTIO
N
specific
get/set
BK_SEL_S
TORED_PO
LL_P_PAT
H
specific
get/set
BK_SEL_S
TORED_PO
LL_C_PAT
H
Data type
Description
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
UINT
maximum instance number of an
object currently created in this
class level of device
Data
Description
type
USINT
module number: 0-Coupler, 1- first module,
2-2.module
table number: 0 ... 256; not all existing
USINT
Register number: 0...255 for the Coupler
(0...63 for modules)
UINT
Register data , Status
USINT
Coupler status: 0x01 module communication
error, 0x08: module diagnostic , 0x80 fieldbus
error
UINT
Module status, 0x8000 to decode a message,
High Byte (Bit14...8): channel number, Low
Byte (Bit7..0) Module number
UINT
number of I/O Bits for analog output data
words
UINT
number of I/O Bits for analog input data
words
UINT
number of I/O Bits for digital output data bits
UINT
number of I/O Bits for digital input data bits
USINT
An enumerator used to specify fieldbus error
handling
0: stop local I/O cycles (default)
1: switch all outputs to 0
2: do nothing
3:switch all outputs to a predefined output
image
UINT
Non volatile power up value for the polled I/O
produced connection path. The attribute is
used to hold an enumerator for the assembly
path and the class and instance for the modu-
les object (discrete input point...) paths.Write
only instance values that are available for
Couplers present module configuration. (e.g.
do not use analog input points if only digital
modules are fixed to the Coupler.
0: bad value, path value not visible
1: analog and digital output data
2: only digital output data
3: only analog output data
4:analog and digital input data,status
5: only digital input data plus status
6: only analog input data plus status
7: analog and digital input data
8: only digital input data
9: only analog input data
UINT
Non volatile power up value for the polled I/O
consumed connection path. The attribute is
used to hold an enumerator for the assembly
path and the class and instance for modules
object (discrete input point ...) paths. Write
DeviceNet • 127