Technical Data - WAGO 750-306 Technical Description

Modular i/o system devicenet
Hide thumbs Also See for 750-306:
Table of Contents

Advertisement

3.2.11

Technical Data

System data
Max. no. of nodes
Max. no. of I/O points
Transmission medium
Max. length of bus line
Baud rate
BusCoupler connection
Programming
IEC 61131-3
Standards and approvals
UL
Conformity marking
Accessories
EDS-Dateien
Miniature WSB quick marking system
Technical data
Max. number of I/O modules
Fieldbus
Input process image
Output process image
Input variables
Output variables
Program memory
Data memory
Non-volatile memory
Cycle time
Configuration
DeviceNet features
Voltage via power jumper contacts
WAGO-I/O-SYSTEM 750
DeviceNet
Feldbus-Koppler/-Controller • 103
Fieldbus Controller 750-806
64 with scanner
ca. 6000 (depends on master)
shielded Cu cable,
trunk line: AWG 15, 18 (2x 0.82mm
drop line: AWG 22, 24 (2x0.2mm
100 m ... 500 m
(baud rate dependent / cable dependent)
125 kBaud, 250 kBaud, 500 kBaud
5-pole male connector, series 231 (MCS)
female connector 231-305/010-000/050-000
is included
WAGO-I/O-PRO 32
IL, LD, FBD, ST, FC
E175199, UL508
E198726
Clas I Div2 ABCD T4A (applied for)
CE
750-912
64
max. 1024 Byte
max. 1024 Byte
max. 512 Byte
max. 512 Byte
128 kByte
64 kByte
8 kByte (retain)
< 3 ms for 1,000 statements /256 dig. I/Os
via PC or control
Polled I/O Message Connection
Strobed I/O Message Connection
Change of State / Cyclic Message Connection
UCMM Device, expandable to master with De-
vNet.lib
DC 24 V (-15 % / + 20 %)
2
2
+2x1.7mm
)
2
2
+2x0.32mm
)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wago-i/o-system 750750-806

Table of Contents