Trending (Data Logger) - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

Advanced EnerVista 469 Setup Features
WARNING

Trending (Data Logger)

GE Multilin
3.
Press the "View" button to display the following window:
VOLTAGE LEVEL
Displays the value
and the angle of
the voltage phasors
VOLTAGE VECTORS
Assigned to Phasor
Set 1, Graph 1
4.
The 469 Motor Management Relay was designed to display lagging angles.
Therefore, if a system condition would cause the current to lead the voltage by
45°, the 469 relay will display such angle as 315° Lag instead of 45° Lead.
When the currents and voltages measured by the relay are zero, the angles
displayed by the relay and those shown by the EnerVista 469 Setup
software are not fixed values.
The trending or data logger feature is used to sample and record up to eight actual
values at an interval defined by the user. Several parameters can be trended and
graphed at sampling periods ranging from 1 second up to 1 hour. The parameters
which can be trended by the EnerVista 469 Setup software are:
Currents/Voltages:
Phase Currents A, B, and C, and Average Phase Current
Motor Load
Current Unbalance
Ground Current
Differential Currents A, B, and C
System Frequency
Voltages Vab, Vbc, Vca Van, Vbn & Vcn
Power:
Power Factor
Real (kW or hp) Reactive (kvar), and Apparent (kVA) Power
Positive Watthours
Positive and Negative Varhours
Torque
http://www.GEindustrial.com/multilin
Motor Management Relay
CURRENT LEVEL
Displays the value
and angle of the
current phasor
CURRENT VECTORS
Assigned to Phasor
Set 2, Graph 2
469
4–27