Fault Setup - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

S13 469 Testing

Fault Setup

FAULT
SETUP
GE Multilin
PATH: SETPOINTS
S13 469 TESTING
[ ]
FAULT CURRENT
PHASE A: 0.00 x CT
FAULT CURRENT
MESSAGE
PHASE B: 0.00 x CT
FAULT CURRENT
MESSAGE
PHASE C: 0.00 x CT
FAULT GROUND
MESSAGE
CURRENT: 0.0 A
FAULT VOLTAGES
MESSAGE
VLINE: 1.00 x RATED
FAULT CURRENT
MESSAGE
LAGS VOLTAGE: 0°
FAULT DIFF AMPS
MESSAGE
IDIFF: 0.00 x CT
FAULT STATOR
MESSAGE
RTD TEMP: 40°C
FAULT BEARING
MESSAGE
RTD TEMP: 40°C
FAULT OTHER
MESSAGE
RTD TEMP: 40°C
FAULT AMBIENT
MESSAGE
RTD TEMP: 40°C
FAULT SYSTEM
MESSAGE
FREQUENCY: 60.0 Hz
FAULT ANALOG
MESSAGE
INPUT 1: 0%
FAULT ANALOG
MESSAGE
INPUT 2: 0%
FAULT ANALOG
MESSAGE
INPUT 3: 0%
FAULT ANALOG
MESSAGE
INPUT 4: 0%
The values entered under Fault Values will be substituted for the measured values in
the 469 when the simulation mode is "Simulate Fault".
http://www.GEindustrial.com/multilin
Motor Management Relay
FAULT SETUP
Range: 0.00 to 20.00 x CT in steps of
0.01
Range: 0.00 to 20.00 x CT in steps of
0.01
Range: 0.00 to 20.00 x CT in steps of
0.01
Range: 0.0 to 5000.0 A in steps of 0.1
Range: 0.00 to 1.10 x RATED in steps of
0.01
Range: 0 to 359° in steps of 1
Range: 0.00 to 1.10 x RATED in steps of
0.01
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: 45.0 to 70.0 Hz in steps of 0.1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
469
5–85

Advertisement

Table of Contents
loading

Table of Contents