S3 Digital Inputs
ASSIGNABLE
INPUT 1
ASSIGNABLE
INPUT 1
ASSIGNABLE
INPUT 1
ASSIGNABLE
INPUT 1
GE Multilin
ASSIGN TRIP RELAYS:
MESSAGE
Trip
GENERAL SWITCH A
MESSAGE
TRIP DELAY: 5.0 s
These setpoints apply only if the
messages appear for General Switches B, C, and D.
There are four general switch functions assignable to the four digital inputs. Once a
general switch function is chosen for one of the digital inputs, the setpoint messages
shown here follow the assignment message. An alarm and/or trip may then be
configured for that input. The alarm and/or trip may be assigned a common name
and a common block time from motor start if required (if the alarm is to be disabled
until some period of time after he motor has been started). A value of "0" for the
setpoint indicates that the feature is always active, when the motor is
BLOCK TIME
stopped or running. The switch may also be defined as normally open or normally
closed. After the block delay has expired, the digital input will be monitored. If the
switch is not in its normal state after the specified delay, an alarm or trip will occur.
m) Capture Trace
PATH: SETPOINTS
S3 DIGITAL INPUTS
[ ]
INPUT 1 FUNCTION:
Capture Trace
Setting the
INPUT 1(4) FUNCTION
command via a switch input. The captured waveforms can be displayed with the
relay software. There are no additional setpoints associated with this value.
n) Simulate Pre-Fault
PATH: SETPOINTS
S3 DIGITAL INPUTS
[ ]
INPUT 1 FUNCTION:
Simulate Pre-Fault
Setting the
INPUT 1(4) FUNCTION
Simulate Pre-Fault mode as per the
setting via a switch input. This is typically used for relay or system testing.
MODE
There are no additional Digital Input setpoints associated with this value.
o) Simulate Fault
PATH: SETPOINTS
S3 DIGITAL INPUTS
[ ]
INPUT 1 FUNCTION:
Simulate Fault
Setting the
INPUT 1(4) FUNCTION
Simulate Fault mode as per the
setting via a switch input. This is typically used for relay or system testing.
MODE
There are no additional Digital Input setpoints associated with this value.
p) Simulate Pre-Fault ...Fault
PATH: SETPOINTS
S3 DIGITAL INPUTS
[ ]
INPUT 1 FUNCTION:
Sim Pre-Fault.Fault
Setting the
INPUT 1(4) FUNCTION
Simulate Pre-Fault to Fault mode as per the
setting via a switch input. This is typically used for relay or system
SIMULATION MODE
testing. There are no additional Digital Input setpoints associated with this value.
http://www.GEindustrial.com/multilin
Motor Management Relay
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 0.1 to 5000.0 s in steps of 0.1
is "General Switch A". Similar
INPUT 1(4) FUNCTION
ASSIGNABLE INPUT 1(4)
Range: See above.
to "Capture Trace" allows for trace capture upon
ASSIGNABLE INPUT 1(4)
Range: See above.
to "Simulate Pre-Fault" allows the user to start the
S13 469 TESTING
SIMULATION MODE
ASSIGNABLE INPUT 1(4)
Range: See above.
to "Simulate Fault" allows the user to start the
S13 469 TESTING
SIMULATION MODE
ASSIGNABLE INPUT 1(4)
Range: See above.
to "Sim Pre-Fault.Fault" allows the user to start the
S13 469 TESTING
469
SIMULATION
SIMULATION
SIMULATION MODE
5–27