GE 469 Instruction Manual page 196

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

469
Motor Management Relay
SPEED2
OVERLOAD SETUP
5–90
d) Voltage Dependent Overload Curves
If the
is set to "Voltage Dependent" in the Thermal Model, the
SELECT CURVE STYLE
following setpoints will appear:
PATH: SETPOINTS
S14 2-SPEED MOTOR
[ ]
SPEED2 TRIP AT
1.01 x FLA: 17414.5 s
SPEED2 TRIP AT
MESSAGE
1.05 x FLA: 3414.9 s
SPEED2 TRIP AT
MESSAGE
1.10 x FLA: 1666.7 s
SPEED2 TRIP AT
MESSAGE
1.20 x FLA: 795.4 s
SPEED2 TRIP AT
MESSAGE
1.30 x FLA: 507.2 s
SPEED2 TRIP AT
MESSAGE
1.40 x FLA: 364.6 s
SPEED2 TRIP AT
MESSAGE
1.50 x FLA: 280.0 s
SPEED2 TRIP AT
MESSAGE
1.75 x FLA: 169.7 s
SPEED2 TRIP AT
MESSAGE
2.00 x FLA: 116.6 s
SPEED2 TRIP AT
MESSAGE
2.25 x FLA: 86.1 s
SPEED2 TRIP AT
MESSAGE
2.50 x FLA: 66.6 s
SPEED2 TRIP AT
MESSAGE
2.75 x FLA: 53.3 s
SPEED2 TRIP AT
MESSAGE
3.00 x FLA: 43.7 s
SPEED2 TRIP AT
MESSAGE
3.25 x FLA: 36.6 s
SPEED2 TRIP AT
MESSAGE
3.50 x FLA: 31.1 s
SPEED2 TRIP AT
MESSAGE
3.75 x FLA: 26.8 s
SPEED2 TRIP AT
MESSAGE
4.00 x FLA: 23.2 s
SPEED2 TRIP AT
MESSAGE
4.25 x FLA: 20.5 s
SPEED2 TRIP AT
MESSAGE
4.50 x FLA: 18.2 s
SPEED2 TRIP AT
MESSAGE
4.75 x FLA: 16.2 s
SPEED2 TRIP AT
MESSAGE
5.00 x FLA: 14.6 s
SPEED2 TRIP AT
MESSAGE
5.50 x FLA: 12.0 s
SPEED2 TRIP AT
MESSAGE
6.00 x FLA: 10.0 s
http://www.GEindustrial.com/multilin
S14 Two-Speed Motor
SPEED2 OVERLOAD SETUP
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
Range: 0.5 to 99999.9 in steps of 0.1
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents