Changing Setpoints

Output Relay Setpoints

Text Setpoints

GE Multilin
Output relays (Trip or Alarm) can be associated to the Auxiliary Relays 2 and 3. Each
can be selected individually, or in combination, in response to customer specific
requirements, which can be initiated by any protection element or function, whose
setpoint has them selected.
ASSIGN RELAYS
1.
Select the
S5 CURRENT ELEM.
message.
ASSIGN TRIP RELAYS:
Trip
2.
If an application requires the short circuit protection element to operate the
Auxiliary Output 3 relay, select this output relay by pressing the value key until
the desired combination appear in the display.
ASSIGN TRIP RELAYS:
Trip & Auxiliary3
3.
Press the ENTER key to store this change into memory. As before, confirmation of
this action will momentarily flash on the display.
NEW SETPOINT HAS
BEEN STORED
Text setpoints have data values, which are fixed in length, but user defined in
character. They may be comprised of uppercase letters, lowercase letters, numerals,
and a selection of special characters. The editing and storing of a text value is
accomplished with the use of the decimal [.], VALUE, and ENTER keys.
For example:
1.
Move to message
S3 DIGITAL INPUTS
and scrolling with the VALUE keys, select "General Sw. A". The relay will display
the following message:
INPUT 1 FUNCTION:
General Sw. A
2.
Press the MESSAGE
key to view the next setpoint,
this user defined input will be changed in this example from the generic
"General Sw. A" to something more descriptive.
3.
If an application is to be using the relay as a station monitor, it is more
informative to rename this input "Station Monitor". Press the decimal [.] key to
enter the text editing mode. The first character will appear underlined as
follows:.
SWITCH NAME:
General Sw. A
4.
Press the VALUE keys until the character "S" is displayed in the first position. Now
press the decimal [.] key to store the character and advance the cursor to the
next position. Change the second character to a "t" in the same manner.
Continue entering characters in this way until all characters of the text "Stn.
Monitor" are entered. Note that a space is selected like a character. If a
character is entered incorrectly, press the decimal [.] key repeatedly until the
cursor returns to the position of the error. Re-enter the character as required.
Once complete, press the ENTER key to remove the solid cursor and view the
result. Once a character is entered, by pressing the ENTER key, it is automatically
saved in flash memory, as a new setpoint.
SWITCH NAME:
Stn. Monitor
http://www.GEindustrial.com/multilin
Motor Management Relay
SHORT CIRCUIT TRIP
ASSIGN TRIP RELAYS
ASSIGNABLE INPUT 1
SWITCH NAME
469
setpoint
,
INPUT 1 FUNCTION
. The name of
1–11

Advertisement

Table of Contents
loading

Table of Contents