A2 Metering Data

Speed

SPEED

Power Metering

POWER
METERING
NOTE
NOTE
GE Multilin
If no VT connection type is programmed for the
SENSING
VT CONNECTION TYPE
flash message will appear when an attempt is made to enter this group of
messages.
PATH: ACTUAL VALUES
A2 METERING DATA
[ ]
TACHOMETER: 0 RPM
If the Tachometer function is assigned to one of the digital inputs, the tachometer
readout may be viewed here.
If no digital input is configured as tachometer in
, the
THIS FEATURE NOT PROGRAMMED
INPUT1(4)
an attempt is made to enter this group of messages.
PATH: ACTUAL VALUES
A2 METERING DATA
[ ]
POWER FACTOR:
0.00
REAL POWER:
MESSAGE
0 kW
REAL POWER:
MESSAGE
O hp
REACTIVE POWER:
MESSAGE
0 kvar
APPARENT POWER:
MESSAGE
0 kVA
POSITIVE WATTHOURS:
MESSAGE
0.000 MWh
POSITIVE VARHOURS:
MESSAGE
0.000 Mvarh
NEGATIVE VARHOURS:
MESSAGE
0.000 Mvarh
TORQUE:
MESSAGE
000.0 Nm
The values for power metering and 3-phase total power quantities are displayed
here. Watthours and varhours can also be seen here.
An induction motor by convention consumes Watts and vars (+Watts and
+vars). A synchronous motor can generate vars (–vars) and feed them
back to the power system.
If the
S2 SYSTEM SETUP
setpoint is not programmed, the
appears when an attempt is made to enter this group of messages.
Real Power (hp) is converted directly from Real Power (kW). This display-
only value is not used for protection functions. This message will not
display more than 65535 hp regardless of the actual kW that are being
metered.
http://www.GEindustrial.com/multilin
Motor Management Relay
S2 SYSTEM SETUP
setpoint, the
THIS FEATURE NOT PROGRAMMED
SPEED
Range: 0 to 7200 RPM
S3 DIGITAL INPUTS
flash message will appear when
POWER METERING
Range: 0.01 to 0.99 Lead or Lag, 0.00,
1.00
Range: 0 to ±99999 kW
Range: 0 to 65535 hp
Range: 0 to ±99999 kvar
Range: 0 to 65535 kVA
Range: 0.000 to 999999.999 MWh
Range: 0.000 to 999999.999 Mvarh
Range: 0.000 to 999999.999 Mvarh
Range: 0.00 to 999999.9 Nm. Seen only
if torque metering is enabled
VOLTAGE SENSING
VOLTAGE TRANSFORMER RATIO
THIS FEATURE NOT PROGRAMMED
469
VOLTAGE
ASSIGNABLE
flash message
6–11