S1 469 Setup

Passcode

PASSCODE

Preferences

PREFERENCES
GE Multilin
S1 469 Setup
PATH: SETPOINTS
S1 469 SETUP
[ ]
ENTER PASSCODE FOR
ACCESS:
SETPOINT ACCESS:
MESSAGE
Permitted
CHANGE PASSWORD:
MESSAGE
No
A passcode access security feature is provided in addition to the setpoint access
jumper. When shipped from the factory, the passcode is defaulted to 0. Passcode
protection is ignored when the passcode is 0. In this case, only the setpoint access
jumper is required for changing setpoints from the front panel. Passcodes are also
ignored when programming setpoints via the RS485 port. However when
programming setpoints using the front RS232 port and the EnerVista 469 Setup
software, a passcode is required (if enabled).
The
ENTER PASSCODE FOR ACCESS
is "Restricted". The
SETPOINT ACCESS
setpoints are seen only if the passcode is 0 and the
To enable passcode protection on a new relay, follow the procedure below:
1.
Press MESSAGE
then MESSAGE
2.
Select "Yes" and follow the directions to enter a new passcode 1 to 8 digits in
length.
3.
Once a passcode (other than "0") is programmed, it must be entered each time
setpoint access is restricted. If a non-zero passcode has been programmed and
setpoint access is restricted, then the
appears when entering the
4.
Enter the correct passcode. A flash message will advise if the code is incorrect
and allows a retry. If the passcode is correct and the setpoint access jumper is
installed, the
SETPOINT ACCESS: Permitted
5.
Setpoints can now be entered. Press ESCAPE to exit the
group and program the appropriate setpoints. If no keys are pressed for 5 min-
utes, programming access will no longer be allowed and the passcode must be
re-entered. Removing the setpoint access jumper or setting the
setpoint to "Restricted" will also immediately disable setpoint access.
ACCESS
If a new passcode is required, gain setpoint access by entering the valid passcode
as described above, then press MESSAGE
message and follow directions. If an invalid passcode is entered, an encrypted
passcode may be viewed by pressing the HELP key. Consult the factory service
department with this number if the currently programmed passcode is unknown.
Using a deciphering program, the passcode can be determined.
PATH: SETPOINTS
S1 469 SETUP
[ ]
DEFAULT MESSAGE
CYCLE TIME: 2.0 s
DEFAULT MESSAGE
MESSAGE
TIMEOUT: 300 s
AVERAGE MOTOR LOAD
MESSAGE
CALC. PERIOD: 15 min.
TEMPERATURE DISPLAY:
MESSAGE
Celsius
http://www.GEindustrial.com/multilin
Motor Management Relay
PASSCODE
Range: 1 to 8 numeric digits
Range: Permitted, Restricted
Range: No, Yes
setpoint is seen only if the passcode is not 0 and
SETPOINT ACCESS
SETPOINT ACCESS
until
CHANGE PASSCODE?
ENTER PASSCODE FOR ACCESS
subgroup.
S1 469 SETUP
PASSCODE
message appears.
to display the
PREFERENCES
Range: 0.5 to 10.0 s in steps of 1
Range: 10 to 900 s in steps of 1
Range: 1 to 90 min. in steps of 1
Range: Celsius, Fahrenheit
469
and
CHANGE PASSWORD
is "Permitted".
is displayed.
message
S1 469 SETUP
PASSCODE
SETPOINT
CHANGE PASSCODE
5–7