GE 469 Instruction Manual page 187

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

S12 Analog Inputs/Outputs
Analog Input Diff 1-2
ANALOG INPUT
DIFF 1-2
NOTE
GE Multilin
PATH: SETPOINTS
S12 ANALOG I/O
[ ]
ANALOG IN DIFF 1-2:
Disabled
ANALOG IN DIFF 1-2
MESSAGE
NAME: Analog 1-2
ANALOG IN DIFF 1-2
MESSAGE
COMPARISON: % Diff
ANALOG IN DIFF 1-2
MESSAGE
LOGIC: 1<>2
ANALOG IN DIFF 1-2
MESSAGE
ACTIVE: Always
A/I DIFF 1-2 BLOCK
MESSAGE
FROM START: 0 s
ANALOG IN DIFF 1-2
MESSAGE
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
ANALOG IN DIFF 1-2
MESSAGE
ALARM LEVEL: 10%
ANALOG IN DIFF 1-2
MESSAGE
ALARM DELAY: 0.1 s
ANALOG IN DIFF 1-2
MESSAGE
EVENTS: Off
ANALOG IN DIFF 1-2
MESSAGE
TRIP: Off
ASSIGN TRIP RELAYS:
MESSAGE
Trip
ANALOG IN DIFF 1-2
MESSAGE
TRIP LEVEL: 10%
ANALOG IN DIFF 1-2
MESSAGE
TRIP DELAY: 0.1 s
This settings menu is seen only if Analog Inputs 1 and 2 are enabled. The
and
DIFF 1-2 TRIP LEVEL
ANALOG IN DIFF 1-2 ALARM LEVEL
"%" if the
ANALOG IN DIFF 1-2 COMPARISON
setpoint if
INPUT 1 UNITS
ANALOG IN DIFF 1-2 COMPARISON
This feature compares two analog inputs and activate alarms or trips based on their
difference, which can be an absolute difference in units or a percentage difference.
The second analog input (2 for 1-2) is used as the reference value for percentage
calculations. The comparison logic can also be selected as one input greater than
the other ("1>2") or vice versa ("2>1") or as absolute difference ("1<>2"). The
compared analog inputs must be programmed with the same units type prior to
programming this feature.
For example, two motors on a dual motor drive are each protected a 469. The
motors should be at the same power level (kW). Connect the analog outputs
(programmed for kW) from both relays to the analog inputs of one relay. Program
the analog input differential to monitor the two motors kW and trip at a
predetermined level.
http://www.GEindustrial.com/multilin
Motor Management Relay
ANALOG INPUT DIFF 1–2
Range: Disabled, Enabled
Range: 12 alphanumeric characters
Range: % Diff, Abs. Diff
Range: 1<>2, 1>2, 2>1
Range: Always, Start/Run
Range: 0 to 5000 s in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
Range: 0.1 to 300.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3 Trip & Auxiliary3
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
Range: 0.1 to 300.0 s in steps of 0.1
setpoints are shown units of
is "%Diff" or in units defined by the
is "Abs Diff".
469
ANALOG IN
ANALOG
5–81