To set the phase CT primary rating, modify the
setpoint as shown below.
PHASE CT PRIMARY
Press the MENU key until the relay displays the setpoints menu header.
[ ]
ENTER
or
[ ]
Press
[ ]
CURRENT
MESSAGE
SENSING
ENTER
or
Press the
displayed, or enter the value directly
To set the phase Motor Full Load Amps FLA, modify the
SENSING
MOTOR FULL LOAD AMPS FLA
Press the MENU key until the relay displays the setpoints menu header.
[ ]
ENTER
or
[ ]
Press
[ ]
CURRENT
MESSAGE
SENSING
or
ENTER
Press the
displayed, or enter the value directly
http://www.GEindustrial.com/multilin
S2 SYSTEM SETUP
Press
[ ]
MESSAGE
ENTER
or
VALUE
keys until 600 A is
via the numeric keypad.
Press the
ENTER
key to store the
setpoint.
setpoint as shown below.
Press
[ ]
MESSAGE
or
ENTER
Press
MESSAGE
VALUE
keys until 318 A is
via the numeric keypad.
ENTER
Press the
key to store the
setpoint.
Changing Setpoints
CURRENT SENSING
PHASE CT PRIMARY:
OFF
PHASE CT PRIMARY:
600 A
NEW SETPOINT HAS
BEEN STORED
S2 SYSTEM SETUP
CURRENT
PHASE CT PRIMARY:
600 A
MOTOR FULL LOAD AMPS
FLA: OFF
MOTOR FULL LOAD AMPS
FLA: 318 A
NEW SETPOINT HAS
BEEN STORED