Output Relays - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

Hardware Functional Testing
ANALOG
EXPECTED
OUTPUT
AMMETER
FORCE
READING
VALUE
0%
0 mA
25%
0.25 mA
50%
0.50 mA
75%
0.75 mA
100%
1.00 mA

Output Relays

FORCE
OPERATION
SETPOINT
1
no
nc
no
1 TRIP
2 AUXILIARY
3 AUXILIARY
4 ALARM
5 BLOCK START
6 SERVICE
All Relays
No Relays
NOTE
GE Multilin
b) 0 to 1 mA Analog Input
1.
Alter the following setpoints:
S12 ANALOG I/O
ANALOG INPUT1
S12 ANALOG I/O
ANALOG INPUT1
S12 ANALOG I/O
ANALOG INPUT1
for Analog Inputs 2 to 4)
2.
Analog output values should be ±0.01 mA on the ammeter. Measured analog
input values should be ±10 units. Force the analog outputs using the following
setpoints:
S13 TESTING
TEST ANALOG OUTPUT
"Enabled"
S13 TESTING
TEST ANALOG OUTPUT
(enter desired percent, repeats for analog output 2-4)
3.
Verify the ammeter readings as well as the measured analog input readings.
View the measured values in
MEASURED AMMETER
READING (mA)
1
2
3
To verify the functionality of the output relays, perform the following steps:
1.
Using the setpoint:
S13 TESTING
TEST OUTPUT RELAYS
select and store values as per the table below, verifying operation
EXPECTED MEASUREMENT
FOR SHORT
2
3
4
5
nc
no
nc
no
nc
no
nc
The 6 SERVICE relay is failsafe or energized normally. Operating the 6 SERVICE
relay causes it to de-energize.
http://www.GEindustrial.com/multilin
"0-1 mA"
ANALOG INPUT1:
ANALOG INPUT1 MINIMUM:
ANALOG INPUT1 MAXIMUM:
FORCE ANALOG OUTPUTS FUNCTION:
ANALOG OUTPUT 1 FORCED VALUE:
A2 METERING DATA
ANALOG INPUTS
EXPECTED
MEASURED ANALOG INPUT
ANALOG
INPUT
4
1
READING
0 mA
250 mA
500 mA
750 mA
1000 mA
FORCE OPERATION OF RELAYS:
ACTUAL MEASUREMENT
FOR SHORT
6
1
2
3
no
nc
no
nc
no
nc
no
469
Motor Management Relay
"0"
"1000" (repeat
"0%"
:
READING (units)
2
3
4
"1 Trip"
4
5
6
nc
no
nc
no
nc
no
nc
7–7