Start Blocks; Digital Inputs - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

469
Motor Management Relay

Start Blocks

START BLOCKS

Digital Inputs

DIGITAL
INPUTS
NOTE
6–8
PATH: ACTUAL VALUES
A1 STATUS
[ ]
NO START BLOCKS
ACTIVE
OVERLOAD LOCKOUT
MESSAGE
BLOCK: 25 min.
START INHIBIT BLOCK
MESSAGE
LOCKOUT TIME: 20 min.
STARTS/HOUR BLOCK
MESSAGE
LOCKOUT TIME: 20 min.
TIME BETWEEN STARTS
MESSAGE
LOCKOUT TIME: 20 min.
RESTART BLOCK
MESSAGE
LOCKOUT: 1200 s
WARNING
MESSAGE
469 NOT PROGRAMMED
Any active blocking functions may be viewed here. The
message is seen only if the Phase CT Primary or Motor FLA setpoints
PROGRAMMED
have not been programmed.
PATH: ACTUAL VALUES
A1 STATUS
[ ]
ACCESS
SWITCH STATE: Open
TEST
MESSAGE
SWITCH STATE: Open
STARTER STATUS
MESSAGE
SWITCH STATE: Open
EMERGENCY RESTART
MESSAGE
SWITCH STATE: Open
REMOTE RESET
MESSAGE
SWITCH STATE: Open
ASSIGNABLE DIGITAL
MESSAGE
INPUT1 STATE: Open
ASSIGNABLE DIGITAL
MESSAGE
INPUT2 STATE: Open
ASSIGNABLE DIGITAL
MESSAGE
INPUT3 STATE: Open
ASSIGNABLE DIGITAL
MESSAGE
INPUT4 STATE: Open
TRIP COIL
MESSAGE
SUPERVISION: No Coil
The messages shown here may be used to monitor Digital Input status. This may be
useful during relay testing or during installation.
Digital Input states will read as shorted if assigned as a tachometer.
http://www.GEindustrial.com/multilin
START BLOCKS
Range: N/A. Message seen when no
start blocks are active
Note: Message seen only after an
overload trip
Range: 0 to 500 min.
Range: 0 to 60 min.
Range: 0 to 500 min.
Range: 0 to 50000 sec.
Note: Seen only if Phase CT Primary
or Motor FLA not programmed
DIGITAL INPUTS
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Open, Shorted
Range: Coil, No Coil
A1 Status
WARNING 469 NOT
GE Multilin