Open Rtd Sensor; Rtd Short/Low Temp - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

S8 RTD Temperature

Open RTD Sensor

OPEN
RTD SENSOR

RTD Short/Low Temp

RTD
SHORT/LOW TEMP
GE Multilin
PATH: SETPOINTS
S8 RTD TEMPERATURE
[ ]
OPEN RTD SENSOR:
Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
OPEN RTD SENSOR
MESSAGE
ALARM EVENTS: Off
The 469 has an Open RTD Sensor alarm. This alarm will look at all RTDs that have
either an alarm or trip programmed and determine if an RTD connection has been
broken. Any RTDs that do not have a trip or alarm associated with them will be
ignored for this feature. When a broken sensor is detected, the assigned output
relay will operate and a message will appear on the display identifying the RTD that
is broken. It is recommended that if this feature is used, the alarm be programmed
as latched so that intermittent RTDs are detected and corrective action may be
taken.
PATH: SETPOINTS
S8 RTD TEMPERATURE
[ ]
RTD SHORT/LOW TEMP
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
RTD SHORT/LOW TEMP
MESSAGE
ALARM EVENTS: Off
The 469 has an RTD Short/Low Temperature alarm. This alarm will look at all RTDs
that have either an alarm or trip programmed and determine if an RTD has either a
short or a very low temperature (less than –50°C). Any RTDs that do not have a trip
or alarm associated with them will be ignored for this feature. When a short/low
temperature is detected, the assigned output relay will operate and a message will
appear on the display identifying the RTD that caused the alarm. It is recommended
that if this feature is used, the alarm be programmed as latched so that intermittent
RTDs are detected and corrective action may be taken.
http://www.GEindustrial.com/multilin
Motor Management Relay
OPEN RTD SENSOR
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: On, Off
RTD SHORT/LOW TEMP
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: On, Off