Pulse Output - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

469
Motor Management Relay

Pulse Output

PULSE
OUTPUT
NOTE
5–76
values are stored in a FIFO (first in, first out) buffer. The buffer size is dictated by
the setpoint demand period. The average value of the buffer is calculated and stored
as the new demand value every minute. Demand for real and reactive power is only
positive quantities (+kW and +kvar).
Demand
where: N = programmed demand period in minutes
n = time in minutes.
160
140
120
100
80
60
40
20
0
t=0
t+10
t+20
FIGURE 5–19: Rolling Demand (15 Minute Window)
PATH: SETPOINTS
S11 MONITORING
[ ]
POS kWh PULSE OUTPUT
RELAY: Off
POS kWh PULSE OUTPUT
MESSAGE
INTERVAL: 1 kWh
POS kvarh PULSE OUT
MESSAGE
RELAY: Off
POS kvarh PULSE OUT
MESSAGE
INTERVAL: 1 kvarh
NEG kvarh PULSE OUT
MESSAGE
RELAY: Off
NEG kvarh PULSE OUT
MESSAGE
INTERVAL: 1 kvarh
RUNNING TIME PULSE
MESSAGE
RELAY: Off
RUNNING TIME PULSE
MESSAGE
INTERVAL: 0 s
This feature configures one or more of the output relays as a pulsed output. When
the programmed interval has transpired the assigned relay will be activated for 1
second.
This feature should be programmed such that no more than one pulse per second
will be required or the pulsing will lag behind the interval activation.
http://www.GEindustrial.com/multilin
N
1
Average
--- -
=
N
N
n
1
=
t+30
t+40
t+50
t+60
t+70
TIME
PULSE OUTPUT
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 kWh in steps of 1
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 kvarh in steps of 1
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 kvarh in steps of 1
Range: Off, Alarm, Auxiliary2,
Auxiliary3
Range: 1 to 50000 s in steps of 1
S11 Monitoring
(EQ 5.12)
t+80
t+90 t+100
808717A1.CDR
GE Multilin