OVERLOAD
CURVE SETUP
5–38
d) Voltage Dependent Overload Curves
If the
is set to "Voltage Dependent" in the Thermal Model, the
SELECT CURVE STYLE
following setpoints will appear:
PATH: SETPOINTS
S5 THERMAL MODEL
[ ]
TIME TO TRIP AT
1.01 x FLA: 17414.5 s
TIME TO TRIP AT
MESSAGE
1.05 x FLA: 3414.9 s
TIME TO TRIP AT
MESSAGE
1.10 x FLA: 1666.7 s
TIME TO TRIP AT
MESSAGE
1.20 x FLA: 795.4 s
TIME TO TRIP AT
MESSAGE
1.30 x FLA: 507.2 s
TIME TO TRIP AT
MESSAGE
1.40 x FLA: 364.6 s
TIME TO TRIP AT
MESSAGE
1.50 x FLA: 280.0 s
TIME TO TRIP AT
MESSAGE
1.75 x FLA: 169.7 s
TIME TO TRIP AT
MESSAGE
2.00 x FLA: 116.6 s
TIME TO TRIP AT
MESSAGE
2.25 x FLA: 86.1 s
TIME TO TRIP AT
MESSAGE
2.50 x FLA: 66.6 s
TIME TO TRIP AT
MESSAGE
2.75 x FLA: 53.3 s
TIME TO TRIP AT
MESSAGE
3.00 x FLA: 43.7 s
TIME TO TRIP AT
MESSAGE
3.25 x FLA: 36.6 s
TIME TO TRIP AT
MESSAGE
3.50 x FLA: 31.1 s
TIME TO TRIP AT
MESSAGE
3.75 x FLA: 26.8 s
TIME TO TRIP AT
MESSAGE
4.00 x FLA: 23.3 s
TIME TO TRIP AT
MESSAGE
4.25 x FLA: 20.5 s
TIME TO TRIP AT
MESSAGE
4.50 x FLA: 18.2 s
TIME TO TRIP AT
MESSAGE
4.75 x FLA: 16.2 s
TIME TO TRIP AT
MESSAGE
5.00 x FLA: 14.6 s
TIME TO TRIP AT
MESSAGE
5.50 x FLA: 12.0 s
TIME TO TRIP AT
MESSAGE
6.00 x FLA: 10.0 s
http://www.GEindustrial.com/multilin
S5 Thermal Model
OVERLOAD CURVE SETUP
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
Range: 0.5 to 99999.9 s in steps of 0.1
GE Multilin