S9 Voltage Elements

Frequency

FREQUENCY
GE Multilin
PATH: SETPOINTS
S9 VOLTAGE ELEM.
[ ]
FREQUENCY
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
OVER FREQUENCY
MESSAGE
ALARM LEVEL: 60.50 Hz
UNDER FREQUENCY
MESSAGE
ALARM LEVEL: 59.50 Hz
FREQUENCY
MESSAGE
ALARM DELAY: 1.0 s
FREQUENCY
MESSAGE
ALARM EVENTS: Off
FREQUENCY
MESSAGE
TRIP: Off
ASSIGN TRIP RELAYS:
MESSAGE
Trip
OVER FREQUENCY
MESSAGE
TRIP LEVEL: 60.50 Hz
UNDER FREQUENCY
MESSAGE
TRIP LEVEL: 59.50 Hz
FREQUENCY
MESSAGE
TRIP DELAY: 1.0 s
Once the frequency of the phase AN or AB voltage (depending on wye or delta
connection) is out of range of the overfrequency and underfrequency setpoints, a
trip or alarm will occur.
This feature may be useful for load shedding applications on large motors. It could
also be used to load shed an entire feeder if the trip was assigned to an upstream
breaker.
http://www.GEindustrial.com/multilin
Motor Management Relay
FREQUENCY
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 25.01 to 70.00 Hz in steps of
0.01
Range: 20.00 to 60.00 Hz in steps of
0.01
Range: 0.0 to 60.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 25.01 to 70.00 Hz in steps of
0.01
Range: 20.00 to 60.00 Hz in steps of
0.01
Range: 0.0 to 60.0 s in steps of 0.1
469
5–67