A5 Event Recorder

Event 01 to Event 256

EVENT 01
<Cause>
GE Multilin
A5 Event Recorder
PATH: ACTUAL VALUES
A5 EVENT RECORDER
[ ]
TIME OF EVENT 01:
00:00:00.0
DATE OF EVENT 01:
MESSAGE
Jan. 01, 1992
MOTOR SPEED DURING
MESSAGE
EVENT01: Low Speed
TACHOMETER DURING
MESSAGE
EVENT01: 0 RPM
A:
MESSAGE
C:
MOTOR LOAD
MESSAGE
EVENT01: 0.00 x FLA
CURRENT UNBALANCE
MESSAGE
EVENT01: 0%
GROUND CURRENT
MESSAGE
EVENT01: 0.00 A
A:
MESSAGE
C:
HOTTEST STATOR
MESSAGE
RTD: 0°C
HOTTEST BEARING
MESSAGE
RTD: 0°C
HOTTEST OTHER
MESSAGE
RTD: 0°C
AMBIENT
MESSAGE
RTD: 0°C
Vab:
MESSAGE
Vca:
Van:
MESSAGE
Vcn:
SYSTEM FREQUENCY
MESSAGE
EVENT01: 0.00 Hz
0
MESSAGE
0
POWER FACTOR
MESSAGE
EVENT01: 0.00
TORQUE
MESSAGE
EVENT01: 0.0 Nm
ANALOG I/P 1
MESSAGE
EVENT01: 0 Units
ANALOG I/P 2
MESSAGE
EVENT01: 0 Units
http://www.GEindustrial.com/multilin
Motor Management Relay
EVENT 01(256)
Range: hour:minutes:seconds
Range: month day, year
Range: High Speed, Low Speed. Seen
if two-speed feature is enabled.
Range: 0 to 3600 RPM. Seen only if a
Digital Input is Tachometer.
Range: 0 to 100000 A
0
B:
0
0
A
EVENT01
Range: 0.00 to 20.00 x FLA
Range: 0 to 100%
Range: 0.00 to 5000.0 A. Not seen if
Ground CT is set as None.
Range: 0 to 5000 A. Seen only if Phase
0
B:
0
Differential CT is set.
0
A Diff. EV01
Range: –50 to 250°C, --- (no RTD). Seen
if at least 1 RTD is set as Stator.
EVENT01
Range: –50 to 250°C, --- (no RTD). Seen
if at least 1 RTD is Bearing.
EVENT01
Range: –50 to 250°C, --- (no RTD). Seen
if at least 1 RTD is set as Other.
EVENT01
Range: –50 to 250°C, --- (no RTD). Seen
if at least 1 RTD is Ambient.
EVENT01
Range: 0 to 20000 A. Not seen if VT
0
Vbc:
0
Connection set as None
0
A
EVENT01
Range: 0 to 20000 A. Seen only if VT
0
Vbn:
0
Connection set as Wye.
0
A
EVENT01
Range: 0.00, 20.00 to 120.00 Hz. Not
seen if VT Connection is None.
Range: –50000 to 50000 kVA. Not seen
kW
0
kVA
if VT Connection is set as None
kvar
EVENT01
Range: 0.01 to 0.99 Lead or Lag, 0.00,
1.00 Not seen if VT Connection
is set as None.
Range: 0 to 999999.9. Seen only if
Torque Metering is Enabled
Range: –50000 to 50000. Not seen if
Analog Input 1 is Disabled.
Range: –50000 to 50000. Not seen if
Analog Input 2 is Disabled.
469
6–27