Motor Management Relay

General Counters

GENERAL
COUNTERS

Timers

TIMERS
6–26
A breakdown of number of trips by type is displayed here. When the total exceeds
50000, all counters reset to 0. This information can be cleared using the
CLEAR DATA
CLEAR TRIP COUNTERS
reflect the programmed analog input name.
PATH: ACTUAL VALUES
A4 MAINTENANCE
[ ]
NUMBER OF MOTOR
STARTS: 0
NUMBER OF EMERGENCY
MESSAGE
RESTARTS: 0
NUMBER OF STARTER
MESSAGE
OPERATIONS: 0
DIGITAL COUNTER
MESSAGE
0 Units
Two of the 469 general counters count the number of motor starts or start attempts
and the number of Emergency Restarts performed to start a given motor over time.
This may be useful information when troubleshooting a motor failure. When either
of these counters exceeds 50000, that counter will reset to 0. This information can
be cleared with the
S1 469 SETUP
setpoint. Another of the 469 General counters will count the number of starter
operations performed over time. This counter is incremented any time the motor is
stopped, either by a trip or normal stop. This may be useful information for starter
maintenance. When the counter exceeds 50000, that counter will reset to 0. This
information may be cleared with the
setpoint. If one of the assignable digital inputs is programmed as
INFORMATION
Digital Counter, that counter measurement will appear here. The counter can be
reset to zero if the counter is of the incrementing type or pre-set to a predetermined
value using the
S1 469 SETUP
PATH: ACTUAL VALUES
A4 MAINTENANCE
[ ]
MOTOR RUNNING HOURS:
0 hr
TIME BETWEEN STARTS
MESSAGE
TIMER: 0 min
STARTS/HOUR TIMERS
MESSAGE
0
One of the 469 timers accumulates the total running time for the Motor. This may be
useful for scheduling routine maintenance. When this timer exceeds 100000, it will
reset to 0. This timer can be cleared using the
setpoint.
RESET MOTOR INFORMATION
The
TIME BETWEEN STARTS TIMER
useful for planning a motor shutdown. The
here.
http://www.GEindustrial.com/multilin
setpoint. Messages relating to analog inputs
GENERAL COUNTERS
Range: 0 to 50000
Range: 0 to 50000
Range: 0 to 50000
Range: 0 to 1 000 000 000. Seen if a
INSTALLATION
S1 469 SETUP
INSTALLATION
CLEAR DATA
PRESET DIGITAL COUNTER
TIMERS
Range: 0 to 100000 hrs.
Range: 0 to 500 min.
Range: 0 to 60 min.
0
0
0
0 min
S1 469 SETUP
value may be viewed here. This value might be
STARTS/HOUR TIMER
A4 Maintenance
S1 469 SETUP
Digital Input is Digital Counter.
RESET MOTOR INFORMATION
RESET STARTER
setpoint.
INSTALLATION
value is also viewable
GE Multilin