Terminal List

3–8
Table 3–1: 469 Terminal List
Terminal
Description
A01
RTD #1 Hot
A02
RTD #1 Compensation
A03
RTD Return
A04
RTD #2 Compensation
A05
RTD #2 Hot
A06
RTD #3 Hot
A07
RTD #3 Compensation
A08
RTD Return
A09
RTD #4 Compensation
A10
RTD #4 Hot
A11
RTD #5 Hot
A12
RTD #5 Compensation
A13
RTD Return
A14
RTD #6 Compensation
A15
RTD #6 Hot
A16
Analog Output Common –
A17
Analog Output 1 +
A18
Analog Output 2 +
A19
Analog Output 3 +
A20
Analog Output 4 +
A21
Analog Shield
A22
Analog In 24 V DC Power Supply +
A23
Analog Input 1 +
A24
Analog Input 2 +
A25
Analog Input 3 +
A26
Analog Input 4 +
A27
Analog Input Common –
B01
RTD Shield
B02
Auxiliary RS485 +
B03
Auxiliary RS485 –
B04
Auxiliary RS485 Common
C01
Access +
C02
Access –
C03
469 Under Test +
C04
469 Under Test –
D01
RTD #7 Hot
D02
RTD #7 Compensation
D03
RTD Return
D04
RTD #8 Compensation
D05
RTD #8 Hot
D06
RTD #9 Hot
D07
RTD #9 Compensation
D08
RTD Return
D09
RTD #10 Compensation
D10
RTD #10 Hot
D11
RTD #11 Hot
D12
RTD #11 Compensation
D13
RTD Return
D14
RTD #12 Compensation
D15
RTD #12 Hot
D16
Starter Status
D17
Emergency Restart
D18
Remote Reset
D19
Assignable Switch 1
D20
Assignable Switch 2
http://www.GEindustrial.com/multilin
Mechanical Installation
Terminal
Description
D21
Assignable Switch 3
D22
Assignable Switch 4
D23
Switch Common
D24
Switch +24 V DC
D25
Computer RS485 +
D26
Computer RS485 –
D27
Computer RS485 Common
E01
1 Trip NC
E02
1 Trip NO
E03
2 Auxiliary Common
E04
3 Auxiliary NC
E05
3 Auxiliary NO
E06
4 Alarm COMMON
E07
5 Block Start NC
E08
5 Block Start NO
E09
6 Service Common
E10
not used
E11
Coil Supervision +
E12
469 Drawout Indicator
F01
1 Trip Common
F02
2 Auxiliary NO
F03
2 Auxiliary NC
F04
3 Auxiliary COMMON
F05
4 Alarm NO
F06
4 Alarm NC
F07
5 Block Start Common
F08
6 Service NO
F09
6 Service NC
F10
not used
F11
Coil Supervision –
F12
469 Drawout Indicator
G01
Phase VT Neutral
G02
Phase A VT •
G03
Differential A CT •
G04
Differential B CT •
G05
Differential C CT •
G06
Phase A CT •
G07
Phase B CT •
G08
Phase C CT •
G09
1A/5A Ground CT •
G10
50:0.025 Ground CT •
G11
Filter Ground
G12
Safety Ground
H01
Phase B VT •
H02
Phase C VT •
H03
Differential A CT
H04
Differential B CT
H05
Differential C CT
H06
Phase A CT
H07
Phase B CT
H08
Phase C CT
H09
1A/5A Ground CT
H10
50:0.025 Ground CT
H11
Control Power –
H12
Control Power +