A1 Status Network Status; Motor Status; Last Trip Data - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

469
Motor Management Relay
NETWORK STATUS

Motor Status

MOTOR STATUS

Last Trip Data

LAST TRIP
DATA
6–4
b) DeviceNet Connection
PATH: ACTUAL VALUES
A1 STATUS
[ ]
DEVICENET PORT:
Not powered
DEVICENET LINK:
MESSAGE
Not online
EXPLICIT CONNECTION:
MESSAGE
Nonexistent
POLLED I/O
MESSAGE
CONNECTN: Nonexistent
COS CONNECTION
MESSAGE
STATUS: Nonexistent
These values appear when the relay is ordered with the DeviceNet (D) option.
PATH: ACTUAL VALUES
A1 STATUS
[ ]
MOTOR STATUS:
Stopped
MOTOR THERMAL
MESSAGE
CAPACITY USED: 0%
ESTIMATED TRIP TIME
MESSAGE
ON OVERLOAD: Never
MOTOR SPEED:
MESSAGE
Low Speed
These messages describe the motor status at any given point in time. If the motor
has been tripped and the 469 has not yet been reset, the
be "Tripped". The
MOTOR THERMAL CAPACITY USED
the Stator and Rotor Thermal Capacity Used. The values for
appear whenever the 469 picks up on the overload curve.
OVERLOAD
PATH: ACTUAL VALUES
A1 STATUS
[ ]
CAUSE OF LAST TRIP:
No Trip to Date
TIME OF LAST TRIP:
MESSAGE
09:00:00.00
DATE OF LAST TRIP:
MESSAGE
Jan 01 1995
MOTOR SPEED DURING
MESSAGE
TRIP: Low Speed
TACHOMETER
MESSAGE
PreTrip: 3600 RPM
A:
MESSAGE
C:
MOTOR LOAD:
MESSAGE
0.00 x FLA PreTrip
http://www.GEindustrial.com/multilin
NETWORK STATUS
Range: Not powered, operational, Data
size error, Unrecoverable fault,
Minor fault
Range: Not online, Online connected,
Online disconnected, Critical
failure, Connection timeout
Range: Nonexistent, Configuring,
Established, Time-out,
Deferred Delete
Range: Nonexistent, Configuring,
Established, Time-out,
Deferred Delete
Range: Nonexistent, Configuring,
Established, Time-out,
Deferred Delete
MOTOR STATUS
Range: Tripped,
Running, Overload
Range: 0 to 100%
Range: 0 to 10000 sec., Never
Range: HIgh Speed, Low Speed. Seen
if two speed motor is enabled
MOTOR STATUS
reflects an integrated value of both
LAST TRIP DATA
Range: see below
Range: hour:min:sec
Range: Month Day Year
Range: High Speed, Low Speed. Seen
if two-speed motor is enabled
Range: 0 to 3600 RPM. Seen if a Digital
Input set as Tachometer.
Range: 0 to 100000 A
0
B:
0
0
A PreTrip
Range: 0.00 to 20.00 x FLA
A1 Status
Stopped,
Starting,
value will
ESTIMATED TRIP TIME ON
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents