S8 RTD Temperature

RTD 11

RTD #11
GE Multilin
PATH: SETPOINTS
S8 RTD TEMPERATURE
[ ]
RTD #11 APPLICATION:
Other
RTD #11 NAME:
MESSAGE
RTD #11 ALARM:
MESSAGE
Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
RTD #11 ALARM
MESSAGE
TEMPERATURE: 80°C
RTD #7 HIGH ALARM:
MESSAGE
Off
HIGH ALARM RELAYS:
MESSAGE
Alarm
RTD #11 HIGH ALARM
MESSAGE
TEMPERATURE: 80°C
RTD #11 ALARM
MESSAGE
EVENTS: Off
RTD #11 TRIP:
MESSAGE
Off
RTD #11 TRIP VOTING:
MESSAGE
RTD #11
ASSIGN TRIP RELAYS:
MESSAGE
Trip
RTD #11 TRIP
MESSAGE
TEMPERATURE: 90°C
RTD 11 defaults to "Other" RTD type. The Other selection allows the RTD to be used
to monitor any temperature that might be required, either for a process or
additional bearings or other. There are individual alarm, high alarm and trip
configurations for this RTD. Trip voting has been added for extra reliability in the
event of RTD malfunction. If enabled, a second RTD must also exceed the trip
temperature of the RTD being checked before a trip will be issued. If the RTD is
chosen to vote with itself, the voting feature is disabled. The RTD name may be
changed if desired.
http://www.GEindustrial.com/multilin
Motor Management Relay
RTD #11
Range: Stator, Bearing, Ambient, Other,
None
Range: 8 alphanumeric characters
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 250°C in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 1 to 250°C in steps of 1
Range: On, Off
Range: Off, Latched, Unlatched
Range: RTD #1 to RTD #12
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 1 to 250°C in steps of 1
469
5–61