Analog Input Diff 1-2; Analog Input Diff 3-4 - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

469
Motor Management Relay

Analog Input Diff 3-4

ANALOG INPUT
DIFF 3-4
NOTE
5–82
PATH: SETPOINTS
S12 ANALOG I/O
[ ]
ANALOG IN DIFF 3-4:
Disabled
ANALOG IN DIFF 3-4
MESSAGE
NAME: Analog 3-4
ANALOG IN DIFF 3-4
MESSAGE
COMPARISON: % Diff
ANALOG IN DIFF 3-4
MESSAGE
LOGIC: 3<>4
ANALOG IN DIFF 3-4
MESSAGE
ACTIVE: Always
A/I DIFF 3-4 BLOCK
MESSAGE
FROM START: 0 s
ANALOG IN DIFF 3-4
MESSAGE
ALARM: Off
ASSIGN ALARM RELAYS:
MESSAGE
Alarm
ANALOG IN DIFF 3-4
MESSAGE
ALARM LEVEL: 10%
ANALOG IN DIFF 3-4
MESSAGE
ALARM DELAY: 0.1 s
ANALOG IN DIFF 3-4
MESSAGE
EVENTS: Off
ANALOG IN DIFF 3-4
MESSAGE
TRIP: Off
ASSIGN TRIP RELAYS:
MESSAGE
Trip
ANALOG IN DIFF 3-4
MESSAGE
TRIP LEVEL: 10%
ANALOG IN DIFF 3-4
MESSAGE
TRIP DELAY: 0.1 s
This settings menu is seen only if Analog Inputs 3 and 4 are enabled. The
and
DIFF 3-4 TRIP LEVEL
ANALOG IN DIFF 3-4 ALARM LEVEL
"%" if the
ANALOG IN DIFF 3-4 COMPARISON
setpoint if
INPUT 3 UNITS
ANALOG IN DIFF 3-4 COMPARISON
This feature compares two of the analog inputs and activate alarms or trips based
on the difference between them. The difference can be of an absolute difference in
units or a percentage difference. The second analog input (4 for 3-4) is used as the
reference value for percentage calculations. The comparison logic can also be
selected as one input greater than the other ("3>4") or vice versa ("4>3") or as
absolute difference ("3<>4"). Note that the compared analog inputs must be
programmed with the same unit type prior to using this feature.
http://www.GEindustrial.com/multilin
S12 Analog Inputs/Outputs
ANALOG INPUT DIFF 3–4
Range: Disabled, Enabled
Range: 12 alphanumeric characters
Range: % Diff, Abs. Diff
Range: 3<>4, 3>4, 4>3
Range: Always, Start/Run
Range: 0 to 5000 s in steps of 1
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
Range: 0.1 to 300.0 s in steps of 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
Range: 0.1 to 300.0 s in steps of 0.1
setpoints are shown units of
is "%Diff" or in units defined by the
is "Abs Diff".
ANALOG IN