Overload Curve Setup - GE 469 Instruction Manual

Motor management relay
Hide thumbs Also See for 469:
Table of Contents

Advertisement

S5 Thermal Model
OVERLOAD
CURVE SETUP
GE Multilin
b) Standard Overload Curves
If the
SELECT CURVE STYLE
following setpoint will appear:
PATH: SETPOINTS
S5 THERMAL MODEL
[ ]
STANDARD OVERLOAD
CURVE NUMBER: 4
If the motor starting times are well within the safe stall times, it is recommended
that the 469 Standard Overload Curve be used. The standard overload curves are a
series of 15 curves with a common curve shape based on typical motor thermal limit
curves (see the figure and table below).
100000
10000
1000
100
10
1.00
0.10
1.00
FIGURE 5–6: 469 Standard Overload Curves
http://www.GEindustrial.com/multilin
is set to "Standard" in the Thermal Model, only the

OVERLOAD CURVE SETUP

Range: 1 to 15 in steps of 1. Seen only
x15
x1
10
MULTIPLE OF FULL LOAD AMPS
469
Motor Management Relay
if Standard curve is selected.
100
1000
806804A5.CDR
5–33

Advertisement

Table of Contents
loading