750/760
Feeder Management Relay
Pulse Output
PULSED OUTPUT
5–96
PATH: SETPOINTS
S6 MONITORING
[ ]
PULSED OUTPUT
FUNCTION: Disabled
POS WATTHOURS PULSED
MESSAGE
RELAYS (3-7): -----
POS WATTHOURS PULSED
MESSAGE
INTERVAL:
NEG WATTHOURS PULSED
MESSAGE
RELAYS (3-7): -----
NEG WATTHOURS PULSED
MESSAGE
INTERVAL:
POS VARHOURS PULSED
MESSAGE
RELAYS (3-7): -----
POS VARHOURS PULSED
MESSAGE
INTERVAL:
NEG VARHOURS PULSED
MESSAGE
RELAYS (3-7): -----
NEG VARHOURS PULSED
MESSAGE
INTERVAL:
The 750/760 can operate selected auxiliary relays after an adjustable interval for
the quantities shown above. Pulses occur at the end of each programmed interval.
Upon power up of the relay the Pulse Output function, if enabled, will continue from
where it was at loss of control power. For example, if control power is removed when
the positive watthours actual value is 16.0 MWh, when control power is re-applied a
pulse will occur at 26 MWh if the interval is set to 10.0 MWh.
Note that the Output relay(s) used for this element must be set to "Self-Resetting"
under
. The pulses will consist of a one second on time and a one
S4 OUTPUT RELAYS
second off time. This feature should be programmed such that no more than one
pulse per two seconds will be required or the pulsing will lag behind the interval
activation.
FIGURE 5–56: Pulsed Output Logic
http://www.GEmultilin.com
PULSED OUTPUT
Range: Disabled,
Alarm, Control
Range: Any combination of the 3 to 7
Auxiliary relays
Range: 0.0 to 6553.5 MWh in steps of
0.1 (auto-ranging)
10.0 MWh
Range: Any combination of the 3 to 7
Auxiliary relays
Range: 0.0 to 6553.5 MWh in steps of
0.1 (auto-ranging)
10.0 MWh
Range: Any combination of the 3 to 7
Auxiliary relays
Range: 0.0 to 6553.5 Mvarh in steps of
0.1 (auto-ranging)
10.0 Mvarh
Range: Any combination of the 3 to 7
Auxiliary relays
Range: 0.0 to 6553.5 Mvarh in steps of
0.1 (auto-ranging)
10.0 Mvarh
S6 Monitoring
Alarm,
Latched
GE Multilin