Frequency - GE MOTOR MANAGEMENT RELAY 469 Instruction Manual

Table of Contents

Advertisement

4 SETPOINT PROGRAMMING
S FREQUENCY
S [ENTER] for more
Once the frequency of the phase AN or AB voltage (depending on wye or delta connection) is out of range of
the overfrequency and underfrequency setpoints, a trip or alarm will occur.
This feature may be useful for load shedding applications on large motors. It could also be used to load shed
an entire feeder if the trip was assigned to an upstream breaker.
GE Power Management
ð

FREQUENCY

ENTER
ALARM: Off
ESCAPE
ASSIGN ALARM RELAYS:
ESCAPE
Alarm
MESSAGE
OVER FREQUENCY
ESCAPE
ALARM LEVEL: 60.50 Hz
MESSAGE
UNDER FREQUENCY
ESCAPE
ALARM LEVEL: 59.50 Hz
MESSAGE
FREQUENCY ALARM
ESCAPE
DELAY: 1.0 s
MESSAGE
FREQUENCY ALARM
ESCAPE
EVENTS: Off
MESSAGE
FREQUENCY
ESCAPE
TRIP: Off
MESSAGE
ASSIGN TRIP RELAYS:
ESCAPE
Trip
MESSAGE
OVER FREQUENCY
ESCAPE
TRIP LEVEL: 60.50 Hz
MESSAGE
UNDER FREQUENCY
ESCAPE
TRIP LEVEL: 59.50 Hz
MESSAGE
FREQUENCY
ESCAPE
TRIP DELAY: 1.0 s
MESSAGE
469 Motor Management Relay
4.10 S9 VOLTAGE ELEMENTS
Range: Off, Latched, Unlatched
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Range: 25.01 to 70.00 Hz, step 0.01
Range: 20.00 to 60.00 Hz, step 0.01
Range: 0.0 to 60.0 sec., step 0.1
Range: On, Off
Range: Off, Latched, Unlatched
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3,
Trip & Auxiliary3
Range: 25.01 to 70.00 Hz, step 0.01
Range: 20.00 to 60.00 Hz, step 0.01
Range: 0.0 to 60.0 sec., step: 0.1
4.10.4 FREQUENCY