Parameter Setting; Register Assignment - WAGO 750-563 Manual

I/o modules fieldbus independent. 2 ao 0/4-20ma / 6-18v dc 16 bit. for wago-i/o-system 750
Table of Contents

Advertisement

20 •
750-563 [2 AO 0/4-20mA / 6-18V DC 16 Bit]

Parameter Setting

2.1.1.9 Parameter Setting

2.1.1.9.1 Register Assignment

The following tables display the assignments and factory settings for the
individual registers. The factory settings are the same for both channels.
Register
16 bit integer value with leading sign.
The manufacturer calibration is active if bit 1 is set in register 32.
Y
DAC
Register
16 bit fixed point value without leading sign.
The manufacturer calibration is active if bit 1 is set in register 32.
Y
DAC
Register
16 bit in X
The substitute value is placed on the output of the module after a system reset or a watchdog
timer overflow (module has received no process data for 100 ms).
The substitute value is selected via register 32, bit 9.
Function
17
Manufacturer calibration offset
= Y
* R18 / 8192 + R17
3
Function
18
Manufacturer calibration gain
= Y
* R18 / 8192 + R17
3
Function
19
Manufacturer substitution value
coordinates, depending on the numeric format.
IN
Memory
Access
RAM
R/W
Memory
Access
RAM
R/W
Memory
Access
RAM
R/W
WAGO-I/O-SYSTEM 750
Factory setting
0xXXXX
Factory setting
0xXXXX
Factory setting
0x0000
I/O Modules

Advertisement

Table of Contents
loading