Product Information Label; Technical Specifications; Table 3-3 Slb Technical Specifications - Lantronix 100-120 VAC SLB User Manual

Branch office manager
Table of Contents

Advertisement

Product Information Label

The product information label on the underside of the SLB branch office manager contains the
following information about each SLB unit:
Part Number
Serial Number Bar Code
Serial Number and Date Code
Regulatory Certifications and Statements

Technical Specifications

Note:
The SLB branch office manager is intended for use in Single Phase systems.
Component
Serial Interface (Device)
Serial Interface (Console)
Power Input
Note:
The max input current is de-rated to figures listed in
Power Outlets
Modem Interface
Network Interface
Power Consumption
SLB™ Branch Office Manager User Guide

Table 3-3 SLB Technical Specifications

Description
(8) RJ45-type 8-conductor connector (DTE)
Speed software selectable (300 to 230,400 baud)
(1) RJ45-type 8-pin connector (DTE)
Speed software selectable (300 to 230,400 baud)
100-120 VAC SLB Model
(2) IEC-60320/C20 inlet, 100-120 VAC, 50/60Hz
(20A Branch Circuit) 16A max input current
200-240 VAC SLB Model
(2) IEC-60320/C20 inlet, 200-240 VAC, 50/60Hz
(20A Branch Circuit) 16A max input current
100-120 VAC SLB Model
(8) NEMA5-20R outlets, 100-120 VAC, 50/60Hz
(20A Branch Circuit) 16A max per outlet, 16A total
Individual current sensor for monitoring power draw on each outlet
Output power switchable via independent relay for each outlet
200-240 VAC SLB Model
(8) IEC C13 outlets, 200-240 VAC, 50/60Hz
(20A Branch Circuit) 10A max per outlet, 16A total
(15.9A max total for China CCC)
Individual current sensor for monitoring power draw on each outlet
Output power switchable via independent relay for each outlet.
Single pole only. Not suitable for two hot line power systems.
RJ11 Jack for connection to internal v92 dial up modem.
Note:
To reduce the risk of fire, use only No. 26 AWG or larger (e.g.,
24 AWG) UL Listed or CSA Certified Telecommunication Line Cord.
Dual 10Base-T/100Base-TX RJ45 Ethernet
Less than 30 watts. Applies only to the operation of the SLB branch
office manager and not to the current it is switching.