Acceptance Test Sto (Extended Functions) - Siemens Sinamics G120 Function Manual

Safety integrated
Hide thumbs Also See for Sinamics G120:
Table of Contents

Advertisement

A.2.2

Acceptance test STO (extended functions)

Figure A-2
Procedure
To perform an acceptance test of the STO function as part of the extended functions, proceed
as follows:
1.
2.
3.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
Acceptance test for STO (Extended functions)
The inverter is ready
● The inverter signals neither faults nor alarms of the safety functions (r0945[0...
7], r2122[0...7]).
● STO is not active (r9722.0 = 0).
Switch on motor
2.1.
Enter a speed setpoint ≠ 0.
2.2.
Switch on the motor (ON command).
2.3.
Check that the correct motor is running.
Select STO
3.1.
Select STO while the motor is running.
3.2.
Check the following:
● If a mechanical brake is not available, the motor coasts down.
A mechanical brake brakes the motor and holds it to ensure that it
remains at a standstill.
● The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).
● The inverter signals the following: "STO is active" (r9722.0 = 1).
A.2 Examples of acceptance tests
Appendix
Status
385