Siemens Sinamics G120 Function Manual page 403

Safety integrated
Hide thumbs Also See for Sinamics G120:
Table of Contents

Advertisement

Acceptance test for SDI positive
The two diagrams show the recommended steps to take during the acceptance test. It differs
depending on the settings you have made for SDI:
● Diagram 1: The "SDI active" feedback signal remains active when the motor is switched
off.
● Diagram 2: The "SDI active" feedback signal becomes inactive when the motor is switched
off.
Figure A-11
Diagram 1 - acceptance for SDI+, "SDI active" remains active when the motor is switched off
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
A.2 Examples of acceptance tests
Appendix
403