5.11 Setting basic functions
Figure 5-5
A filter in the inverter suppresses brief signals as a result of the bit pattern test or contact
bounce.
Figure 5-6
The filter extends the response time of the safety function by the debounce time.
Parameter
p9650
p9651
For SIMATIC ET 200pro FC-2, the tolerance time is always 0 ms.
1)
Debounce times for standard and safety functions
The debounce time p0724 for "standard" digital inputs has no influence on the fail-safe digital
input signals. Conversely, the same applies: The debounce time of the fail-safe digital inputs
does not affect the signals of the "standard" inputs.
If you use an input as a standard input, set the debounce time using parameter p0724.
If you use an input as a fail-safe digital input, set the debounce time as described above.
130
Inverter response to a bit pattern test
Filter to suppress brief signals
Description
F-DI switchover discrepancy time (factory setting: 500 ms)
1)
Tolerance time to change over the fail-safe digital input for the basic functions.
STO debounce time (factory setting: 1 ms)
Debounce time of the fail-safe digital input for the basic functions.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD