Siemens Sinamics G120 Function Manual page 295

Safety integrated
Hide thumbs Also See for Sinamics G120:
Table of Contents

Advertisement

STOP F
If a safety function is active
● Fault F01611 immediately initiates a STOP A.
● For message C01711, the inverter response depends on the active safety function:
– When STO is active, then the inverter initiates a STOP A.
– In all other cases, the inverter initiates a STOP B.
If none of the safety functions are active, then the inverter responds as follows:
● Fault F01611 immediately initiates a STOP A.
● There is no immediate stop response for message C01711. However, the message is kept.
When selecting a safety function, the inverter responds with a stop as described above.
The SSM function is considered as active safety function if the SSM filter and the SSM
1)
hysteresis have been enabled.
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
, a STOP F initiates a STOP A or STOP B:
1)
Operation
6.10 Stop responses
295

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents