Parameter
p0010 = 95
p9601
p9761
p9762
p9763
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
5.9 Configuring safety functions and PROFIsafe using STARTER
Description
Drive commissioning parameter filter
Safety Integrated commissioning
Enable functions integrated in the drive (factory setting: 0000 bin)
Functions that have been
enabled:
0 hex
None
1 hex
Basic functions via on‐
board terminals
4 hex
Extended functions via
onboard terminals
8 hex
Basic functions via PRO‐
FIsafe
9 hex
● Basic functions via
PROFIsafe
● Basic functions via
onboard terminal
C hex
Extended functions via
PROFIsafe
D hex
● Extended functions
via PROFIsafe
● Basic functions via
onboard terminals
Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 ... FFFF FFFF.
New password
Confirm password
Functions that have been enabled:
80 hex
STO via Power Module terminals
81 hex
● Basic functions via onboard terminals
● STO via Power Module terminals
84 hex
● Extended functions via onboard
terminals
● STO via Power Module terminals
88 hex
● Basic functions via PROFIsafe
● STO via Power Module terminals
89 hex
● Basic functions via PROFIsafe
● Basic functions via onboard terminals
● STO via Power Module terminals
8C hex
● Extended functions via PROFIsafe
● STO via Power Module terminals
8D hex
● Extended functions via PROFIsafe
● Basic functions via onboard terminals
● STO via Power Module terminals
Commissioning