System properties
8.5 Response times after selection
Table 8-8
Function Selec‐
SS1
SBC
T = p9652
1)
When p9651 > 0: t_E = p9651 + 3 ms; p9651: Delays
2)
When p9651 = 0: t_E = 4 ms
Table 8-9
Function Selec‐
SS1
SBC
When p10017 > 0: t_E = p10017 + 3 ms; p10017: Debounce time
1)
When p10017 = 0: t_E = 4 ms
T depends on how safety function SS1 is set:
2)
● SS1 with braking ramp monitoring: T = p9582 + time to brake down to standstill detection
● SS1 with acceleration monitoring: T = the lower of the two times:
– p9556
– Time to brake down to standstill detection
378
Response times when using the basic functions
Response
tion via
F-DI
STO is active
Signal change at the output
of the Safe Brake Relay
Response times when using the extended functions
Response
tion via
F-DI
STO is active
Signal change at the output
of the Safe Brake Relay
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Response time
Worst case for a fault-
free inverter
4 ms + T
+ t_E
2)
1)
8 ms + T
+ t_E
2)
1)
Response time
Worst case for a fault-
free inverter
50 ms + T
+ t_E
2)
1)
52 ms + T
+ t_E
2)
1)
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
Worst case for an inver‐
ter fault
6 ms + T
+ t_E
2)
1)
22 ms + T
+ t_E
2)
1)
Worst case for an inver‐
ter fault
52 ms + T
+ t_E
2)
1)
60 ms + T
+ t_E
2)
1)